External safety or low gas pressure
Blocking: it retries by itself
On the Quinta, an external safety device connected to the boiler has opened its contact during a heat demand: the boiler blocks for at least 120 seconds and tries to start again once the contact has closed. On the Gas 210, 310 and 610 Eco fitted with the minimum gas pressure switch (option), the gas pressure is too low: the boiler blocks and starts again by itself as soon as the gas pressure is back.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check that the boiler's gas tap is open.
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show b26?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code b26
The meaning depends on the boiler: find yours below.
The contacts of the external safety device are open during a heat demand
Gas pressure switch LD signals too low a pressure (if fitted, option)
If the minimum gas pressure switch LD is connected (option)
The boilers that show this code
What our technician checks
- Quinta: the external safety device connected to the boiler and its contact
- The gas supply and the gas tap
- The setting of the minimum gas pressure switch (LD)
- The wiring and connections of the pressure switch