No flame after several start attempts
Breakdown: the boiler is stopped
The boiler has tried several times to light its burner, 5 times (2 times on the W40/60-m Eco), without getting a flame or without detecting enough ionisation current, and has locked out with the digits flashing. It only restarts after a reset; on the Gas 210 Eco, code 0.2 (with a dot) is a different fault: the fully open position of the air/gas mixing system (SMI) is not detected.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check that the boiler's gas tap is open; if it is closed, open it.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 02?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 02
The meaning depends on the boiler: find yours below.
End position of the SMI flag not detected
No flame formation (after 5 starts)
No flame formation (after five starts)
No flame or no ionisation (after 5start attempts)
No flame formation (after two starts)
The boilers that show this code
What our technician checks
- The gas tap, the gas supply pressure and purging of the gas line
- The ignition cable, its cap and the electrode (breakdown)
- The electrode gap (3 to 4 mm), cleanliness, fitting and earthing
- The gas valve being powered and opening at ignition
- The air/gas ratio and the CO2 at low and full power
- The air inlet, the flue and the condensate trap (blockage, flue gas recirculation)
- The ionisation current and current leaks on the temperature sensors (moisture)
- Gas 210 Eco (code 0.2): the light sensor, the setting of the SMI 100 % flag, the wiring, then the SMI board