Wrong setting or insufficient air flow
Breakdown: the boiler is stopped
On the Quinta, this is a wrong parameter setting; on the Gas 210, 310 and 610 Eco and the W40/60-m Eco, the boiler does not detect enough air flow, because the air inlet, the flue, the condensate trap or the heat exchanger may be blocked, or the air pressure switch is faulty. In both cases the boiler locks out with the digits flashing; as a blocked duct may be the cause, our technician puts it back into service.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Do not reset the boiler: call us.
Does your boiler show 08?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 08
The meaning depends on the boiler: find yours below.
Wrong setting
The air pressure switch does not close
The differential air pressure sensor does not reach the control level
Air transport (safety lockout if there is no signal after a restart)
The boilers that show this code
What our technician checks
- Quinta: parameter D, whose second digit must be 0
- The air inlet and the flue: blockage or fitting error
- The condensate trap and the heat exchanger (fouling)
- The air pressure switch (or sensor) and its connections
- W40/60-m Eco: the spring flap and the gas/air connections (loose or blocked)