Low dynamic pressure, pump blocked or no signal
Breakdown: the boiler is stopped
On a Thision S Plus or Trigon S Plus, the boiler finds a dynamic water pressure that is too low, a blocked boiler pump or a missing control signal (PWM) for that pump: the water is not flowing enough through the boiler, and too low a flow stops the burner at once. It is a lockout: the warning symbol appears, the code flashes, and the boiler only restarts after a reset, once the cause has been removed.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check the water pressure on the analogue gauge or with the Info button: if it is low, top up the system as the user manual explains.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 430?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 430
The meaning depends on the boiler: find yours below.
Dynamic water pressure lower / Pump blocked* / PWM signal missing
What our technician checks
- The boiler pump, to be freed by hand first
- The pump's PWM control signal and its wiring
- The system water pressure (at least 1.0 bar on the Trigon S Plus)
- The hydraulic connection, which must keep the water flowing whenever the burner runs
- The pump minimum and maximum speeds (lines 2322 and 2323)