Elco Fault code Elco
381

No flame at ignition: retries used up

Breakdown: the boiler is stopped

On a Trigon S Plus, the burner has failed several times to form a flame within the ignition safety time, until the number of allowed new attempts ran out (no flame within safety time repetition counter expired). It is a lockout: the warning symbol appears, the code flashes, and the boiler only restarts after a reset, once the cause has been removed.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 381?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 381

The meaning depends on the boiler: find yours below.

381

Repetition counter no flame during the safety time expired

Breakdown: the boiler is stopped Trigon S Plus

What our technician checks

  • The fault history (lines 6800 onward) and the software diagnostic code (line 6705), to find the recorded ignition failures
  • The dynamic gas pressure (17 to 25 mbar)
  • Purging the gas line and the gas valve
  • The ignition and ionisation electrode (wear, damage) and the ionisation current, above 4 µA at full output
  • The gas flow rate (plausibility check)
  • The flue and air supply connections, clear and not reduced