Repeated stray flame signal: retries used up
Breakdown: the boiler is stopped
On a Thision S Plus or Trigon S Plus, the flame monitoring has repeatedly seen extraneous light, a flame signal at a moment when there should be none, until the number of allowed new attempts ran out. It is a lockout: the warning symbol appears, the code flashes, and the boiler only restarts after a reset, once the cause has been removed.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 379?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 379
The meaning depends on the boiler: find yours below.
Repetition counter extraneous light expired
What our technician checks
- The fault history (lines 6800 onward) and the software diagnostic code (line 6705), to find the recorded extraneous light faults
- The ignition and ionisation electrode (wear, damage) and the ionisation current, above 4 µA at full output
- The gas tap, the gas control block and the venturi block: operation and tightness