Elco Fault code Elco
349

Buffer return valve Y15 not available

Breakdown: the boiler is stopped

The controller reports that the buffer tank return valve (Y15) is missing: none of its outputs is set for that valve. On a Trigon XXL, a Thision S Plus or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 349?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 349

The meaning depends on the boiler: find yours below.

349

Buffer return valve Y15 not available

Breakdown: the boiler is stopped Trigon XXL
349

Buffer return valve Y15 missing

Breakdown: the boiler is stopped Thision S Plus, Trigon S Plus

What our technician checks

  • The relay output assigned to the buffer tank return valve Y15 (lines 5890 to 5892 on the boiler, 6030 to 6038 on the extension modules)
  • The relay output test (line 7700): the output switches on and its wiring is correct

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.