Elco Fault code Elco
336

Sensor input BX22 has no function

Breakdown: the boiler is stopped

The controller reports that sensor input BX22 of an extension module (EM1, EM2 or EM3) has no function: the setting of that input does not match what is connected to it. On a Trigon XXL or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 336?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 336

The meaning depends on the boiler: find yours below.

336

Sensor BX22 no function (EM1, EM2 or EM3)

Breakdown: the boiler is stopped Trigon S Plus, Trigon XXL

What our technician checks

  • The setting of input BX22 of the extension modules (lines 6041, 6043 and 6045) and the sensor wired to it
  • The temperature read on input BX22 in the input test (lines 7831, 7833 and 7835)

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.