Elco Fault code Elco
326

Same sensor on BX and mixing group

Breakdown: the boiler is stopped

The same sensor is set twice, on a BX sensor input of the boiler and for the mixing valve group: this is a mistake in the installation settings. On a Trigon XXL, a Thision S Plus or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 326?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 326

The meaning depends on the boiler: find yours below.

326

BX / mixing group same sensors

Breakdown: the boiler is stopped Trigon XXL
326

BX / mixing group same sensor

Breakdown: the boiler is stopped Thision S Plus, Trigon S Plus

What our technician checks

  • The functions set on the BX sensor inputs of the boiler (lines 5930 to 5933)
  • The function set for mixing valve group 1 of the boiler (line 6014)