Elco Fault code Elco
320

DHW charging temperature sensor fault

Breakdown: the boiler is stopped

There is a fault on the sensor that measures the domestic hot water charging temperature (sensor B36). On a Trigon XXL, a Thision S Plus or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 320?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 320

The meaning depends on the boiler: find yours below.

320

DHW charging temperature sensor error

Breakdown: the boiler is stopped Trigon XXL
320

DHW charging temperature sensor fault

Breakdown: the boiler is stopped Thision S Plus, Trigon S Plus

What our technician checks

  • The sensor input the DHW charging sensor B36 is assigned to (lines 5930 to 5933 on the boiler, 6040 to 6045 on the extension modules)
  • The sensor's resistance, measured with the boiler switched off and as close to the sensor as possible, against the maker's values
  • The temperature the controller reads on that input, in the input test (lines 7820 to 7835)
  • The software diagnostic code and the fault history (lines 6705 and 6800 onwards)