Pump monitoring fault after flame on
Breakdown: the boiler is stopped
Once the flame is lit, the controller checks that the boiler pump is working, and that check has failed. On a Trigon XXL or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 193?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 193
The meaning depends on the boiler: find yours below.
Pump supervision error after flame on
Pump monitoring fault after flame ignition
What our technician checks
- The pump operation and its direction of rotation
- Air in the pump motor and in the system (venting function)
- The water flow through the boiler, within the maker's limits
- On a Trigon S Plus, the flow monitoring (contact H7, line 7874)
- The water pressure and water quality of the system
- The software diagnostic code and the fault history (lines 6705 and 6800 onwards)