Elco Fault code Elco
174

Alarm contact H3 or H7 active

Breakdown: the boiler is stopped

The alarm contact on input H3 or input H7 of the controller is active: an external device wired to one of those inputs is reporting a problem. On a Trigon XXL, a Thision S Plus or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.

Does your boiler show 174?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 174

The meaning depends on the boiler: find yours below.

174

Alarm contact H3 or H7 active

Breakdown: the boiler is stopped Thision S Plus, Trigon S Plus, Trigon XXL

What our technician checks

  • The device wired to input H3 or H7 that raised the alarm, and the cause of that alarm
  • The function set for input H3 (line 5960) and its contact action, normally closed or normally open (line 5961)
  • The state of contacts H3 and H7 in the input test (lines 7855 and 7874)
  • On a Trigon S Plus, the water flow monitoring on input H7: the boiler is locked when H7 is open
  • The operation and setting of all connected safety devices
  • The software diagnostic code and the fault history (lines 6705 and 6800 onwards)