Return warmer than the flow
Breakdown: the boiler is stopped
The water coming back from the system (the return) is warmer than the water leaving for the heating (the flow): the water is flowing poorly or the wrong way, or the flow and return sensors are swapped, badly fitted or faulty. On the AMC, AMC Pro Evo, C 230 Evo, MCR-S, MPX2 Compact, Virtuens, Modulens O AFC-S, CFU and CFU C it is a lockout: the boiler stops and only starts again once the cause has been removed and the boiler has been reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show E01.12?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code E01.12
The meaning depends on the boiler: find yours below.
Return > Flow
The temperature measured by the return sensor is higher than the flow temperature
The temperature measured by the return sensor is higher than the flow temperature
The return temperature value is higher than the flow temperature
Return > Flow
What our technician checks
- Water circulation: direction, pump and valves
- Direction, position and connection of the flow and return sensors
- The wiring and connectors of the sensors
- How the sensors are fitted, and their resistance
- The return temperature in the boiler and how the sensors work
- The sensor, replaced if it is faulty
- MPX2 Compact, Virtuens: the CN1 and CN2 settings, then the circuit board if the problem persists