No flame at ignition (oil)
Breakdown: the boiler is stopped
During the ignition safety time, the boiler detects no flame, or the oil preheater does not give its release. Depending on the number shown next to the code, it tries again by itself or locks out.
What you can do
- Write down the code shown, the number next to it if there is one, and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 6U?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
Choose a real expert
Ecowatt is an approved Buderus System Partner: factory training in Germany, direct access to spare parts, one contact.
The variants of code 6U
The small number shown beside the code tells which.
No flame during the safety time
No flame during the safety time
No release from the oil preheater
The boilers that show this code
What our technician checks
- The burner pressure switch (tripped or not)
- The fresh air supply and the flue (blockage)
- The conditions in the boiler room: temperature, supply voltage; let the burner motor cool down
- The oil supply and, if there is one, the safety solenoid valve
- Dirt buildup in the boiler and on the flame sensor; the flame signal
- The ignition (relay test), the electrode gap and condition, the contacts
- The burner setting, the nozzle, the preheater shutoff valve, the mixing system and the solenoid valve
- The oil preheater connector; preheater replaced if necessary