Heating water hotter than expected
Blocking: it retries by itself
The water temperature measured in the boiler is above the set point, or above 95 °C at the flow, return or safety sensor, or too high at the hot water sensor. This is not a lockout: the boiler restarts by itself as soon as the cause is gone.
What you can do
- Write down the code shown, the number next to it if there is one, and the boiler model (on the rating plate).
- Check the water pressure: at least 1 bar, or the needle in the green zone of the pressure gauge. Too low? Top up with the boiler cold, the way your installer showed you.
- Check that enough radiators are open.
- Bleed the radiators, then check the water pressure again.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 0Y?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
Choose a real expert
Ecowatt is an approved Buderus System Partner: factory training in Germany, direct access to spare parts, one contact.
The variants of code 0Y
The small number shown beside the code tells which.
The current flow temperature is higher than the set flow temperature
The temperature at the flow temperature sensor is > 95 °C
The temperature measured by the safety temperature sensor is higher than 95 °C
The temperature measured by the return temperature sensor is higher than 95 °C
The temperature at the DHW temperature sensor is too high
The boilers that show this code
What our technician checks
- The operating pressure and venting of the system and the boiler
- The water flow rate in the system, with the isolation valves fully open
- The heating pump: connection, start-up, pump output or pump curve setting, replaced if needed
- The flow, return and safety sensors and their cables (open circuit, short circuit)
- The hot water sensor: mounting position, cable, sensor replaced if needed
- The KIM (GB072, GB172), properly inserted, replaced if needed
- The set heating water temperature, the heating curve and the cylinder sensor (GB162)