Solar collector sensor B6 not available
Breakdown: the boiler is stopped
The controller reports that the solar collector sensor (B6) is missing: none of its sensor inputs is set for that sensor. On a Trigon XXL, a Thision S Plus or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset; on a Straton XL the controller reports a technical fault, which our technician has to fix.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- On a Trigon XXL, a Thision S Plus or a Trigon S Plus, the boiler locks out: one reset is allowed.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
- On a Straton XL, do not reset the boiler: the controller is reporting a technical fault.
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 341?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 341
The meaning depends on the boiler: find yours below.
Solar Collector sensor B6 not available
Collector sensor B6 missing
Collector pump B6 missing
What our technician checks
- The sensor input the solar collector sensor B6 is assigned to (lines 5930 to 5933 on the boiler, 6040 to 6045 on the extension modules)
- The solar collector sensor type, NTC or Pt 1000 (line 6097)
- The sensor's resistance, measured with the boiler switched off and as close to the sensor as possible, against the maker's values