Solar collector pump Q5 not available
Breakdown: the boiler is stopped
The controller reports that the solar collector pump (Q5) is missing: none of its outputs is set for that pump. On a Trigon XXL, a Thision S Plus or a Trigon S Plus this code is one of the lockouts: the boiler stops and the cause must be removed before it is reset; on a Straton XL the controller reports a technical fault, which our technician has to fix.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- On a Trigon XXL, a Thision S Plus or a Trigon S Plus, the boiler locks out: one reset is allowed.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
- On a Straton XL, do not reset the boiler: the controller is reporting a technical fault.
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 339?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 339
The meaning depends on the boiler: find yours below.
Collector pump Q5 not available
Collector pump Q5 missing
What our technician checks
- The relay output assigned to the solar collector pump Q5 (lines 5890 to 5892 on the boiler, 6030 to 6038 on the extension modules)
- The relay output test (line 7700): the output switches on and its wiring is correct