Stray flame detected
Breakdown: the boiler is stopped
The boiler detects a flame when there should be none: ionisation current without a flame, a faulty ignition transformer or gas valve, or a burner that keeps glowing (CO2 too high on the Innovens MCA, O2 too low on the Modulens G AGC). It is a fault: the boiler stops and only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show L16?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code L16
The meaning depends on the boiler: find yours below.
FLAM.PARASI.
The boilers that show this code
What our technician checks
- The ionisation current measured without a flame
- The ignition transformer
- The gas valve
- The combustion setting: CO2 (Innovens MCA) or O2 (Modulens G AGC)