Stray flame detected at burner 2
Breakdown: the boiler is stopped
The flame detection cell of burner 2 picks up a flame signal before the oil solenoid valve has even opened, when there should be none: a dirty combustion head, a damaged detection cell or a faulty oil solenoid valve. On the Modulens O AFC-S it is a lockout: the boiler stops, the screen flashes red, and it only starts again once the cause has been removed and the boiler has been reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show E07.33?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code E07.33
The meaning depends on the boiler: find yours below.
Burner parasitic flame 2
What our technician checks
- Cleanliness of the combustion head and the mirror
- Condition of the flame detection cell, replaced if necessary
- The oil solenoid valve, replaced if necessary
- The oil pump, to be replaced if the fault persists