Buderus Fault code Buderus
207

Water pressure too low

Blocking: it retries by itself

The water pressure in the heating system is too low (less than 0.2 bar on the GB192i and the GB162). The boiler stops temporarily and restarts by itself as soon as the pressure is restored.

What you can do

  1. Write down the code shown, the number next to it if there is one, and the boiler model (on the rating plate).
  2. Check the water pressure: at least 1 bar, or the needle in the green zone of the pressure gauge. Too low? Top up with the boiler cold, the way your installer showed you.
  3. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show 207?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

Buderus

Choose a real expert

Ecowatt is an approved Buderus System Partner: factory training in Germany, direct access to spare parts, one contact.

The variants of code 207

The small number shown beside the code tells which.

207

The operating pressure is too low, below 0.2 bar

Blocking: it retries by itself GB192i

The boilers that show this code

What our technician checks

  • Filling the system to 2 bar, then venting
  • The expansion vessel
  • The tightness of the system, any leak repaired before filling
  • The pressure switch or pressure sensor: wiring and operation; replaced if needed

The same fault on other boilers

Recent boilers show alone the number older ones show beside the code.