Servomotor or speed drive tolerance error
Breakdown: the boiler is stopped
On a WL30 or WL40 oil burner (W-FM 25 control box), the air servomotor or the variable speed drive is out of tolerance, and the first detailed code (key [+]) tells more: 01h or 05h air servomotor, 02h or 06h speed drive, 00h or 04h either, 07h time ran out during calibration or in setting mode. The burner is locked out and the code flashes on the display.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 65h?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 65h
The small number shown beside the code tells which.
Air actuator or speed controller tolerance error
Air actuator tolerance error.
Speed controller tolerance error
Air actuator or speed controller tolerance error
Air actuator tolerance error.
Speed controller tolerance error
Time elapsed during calibration
What our technician checks
- Free movement of the air damper and the angle drive
- The air servomotor, to be replaced
- The variable speed drive and the fan, replaced if needed
- The key pressed in time during calibration (20 seconds) or in setting mode (30 minutes) (07h)
The same fault on other boilers
Recent boilers show alone the number older ones show beside the code.