Fan speed deviation
Breakdown: the boiler is stopped
On a WL30 or WL40 oil burner (W-FM 25 control box), the fan speed deviates from its set value, and the first detailed code (key [+]) tells more: 01h deviation for too long, 02h deviation too large, 03h speed value out of tolerance for too long. The burner is locked out and the code flashes on the display.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 41h?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 41h
The small number shown beside the code tells which.
The speed deviation lasts too long.
The speed deviation is too large
Speed setpoint outside tolerance for too long
What our technician checks
- Parameters 44 and 45 (01h, 03h)
- The inductive speed sensor (02h)
- The burner setting, to be redone (03h)
The same fault on other boilers
Recent boilers show alone the number older ones show beside the code.
Related codes
From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.