Viessmann Fault code Viessmann
544

Circuit 2 flow sensor open circuit

Blocking: it retries by itself

The flow temperature sensor of heating circuit 2 (the mixing valve circuit) is open-circuit, or this circuit was set up wrongly at commissioning. The boiler keeps running, but this circuit goes into emergency mode: its mixing valve closes and its pump keeps running, so the rooms it heats may cool down.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Does the code stay on or come back? Do not take anything apart: call us.

Does your boiler show 544?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 544

The meaning depends on the boiler: find yours below.

544

Open circuit of the flow temperature sensor of heating circuit 2 with mixing valve

Blocking: it retries by itself Vitodens 100-W B1HF

What our technician checks

  • The flow temperature sensor of mixing valve 2
  • The voltage at the sensor input on the electronic module: 3.3 V with the sensor disconnected
  • The setting in the commissioning assistant, corrected if needed
  • The setting of the ADIO rotary switch

Related codes

From the manufacturer's service manuals for Belgium. Each appliance has its own features: if in doubt, call us.