Circuit 2 flow sensor open circuit
Blocking: it retries by itself
The flow temperature sensor of heating circuit 2 (the mixing valve circuit) is open-circuit, or this circuit was set up wrongly at commissioning. The boiler keeps running, but this circuit goes into emergency mode: its mixing valve closes and its pump keeps running, so the rooms it heats may cool down.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 544?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 544
The meaning depends on the boiler: find yours below.
Open circuit of the flow temperature sensor of heating circuit 2 with mixing valve
What our technician checks
- The flow temperature sensor of mixing valve 2
- The voltage at the sensor input on the electronic module: 3.3 V with the sensor disconnected
- The setting in the commissioning assistant, corrected if needed
- The setting of the ADIO rotary switch