Flame signal too high during calibration
Breakdown: the boiler is stopped
During the automatic calibration of its combustion, shortly after the burner starts, the boiler measures an ionisation current (the flame signal) that is too high: the electrode is not at the right distance from the burner gauze, or the combustion air carries dust or products that leave deposits on the electrodes. The burner locks out and the boiler only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Keep paint, solvent and cleaning product fumes, and building dust, away from the boiler.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 468?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 468
The meaning depends on the boiler: find yours below.
Ionisation current too high during calibration
What our technician checks
- The gap between the ionisation electrode, or ignition and monitoring electrode, and the burner gauze
- Dust in the combustion air (building work, for example)
- The causes of deposits in the boiler room and flue system (detergents, cleaning or personal care products)
- After replacing the burner gauze and the electrode, cleaning of the fan unit, the gas-air duct and the venturi extension
- Unlocking the appliance