Ionisation current implausible against previous value
Blocking: it retries by itself
The ionisation current, the signal the boiler uses to monitor its flame, differs from the previous value in a way that is not plausible. The burner restarts by itself, but if the code keeps coming back, our technician needs to check the electrode, the flue and the gas valve inlet.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
- Keep paint, solvent and cleaning product fumes, and building dust, away from the boiler.
Does your boiler show 376?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 376
The meaning depends on the boiler: find yours below.
Difference in ionisation current compared with the previous value not plausible
What our technician checks
- The ionisation electrode or ignition/monitoring electrode and its connecting cable
- The plug connections (loose contacts)
- The flue system and any flue gas recirculation
- Condensate build-up in the system
- The inlet of the combined gas valve and its strainer (fouling, visual check)
- The source of deposits on the electrodes in the boiler room and the flue system (detergents, cleaning or personal care products)
- After replacing the burner grid and the electrode: cleaning the fan unit, the gas-air duct and the Venturi extension
- Removing the fan unit before the burner, to avoid water damage