Viessmann Fault code Viessmann
372

Repeated flame loss during calibration

Breakdown: the boiler is stopped

During the automatic calibration of its combustion, the boiler lost its flame several times. The burner locks out and the boiler only starts again after a reset.

What you can do

  1. Write down the code shown and the boiler model (on the rating plate).
  2. Reset the boiler once only.
  3. If the code comes back, do not keep trying and do not take anything apart: call us.
  4. Keep paint, solvent and cleaning product fumes, and building dust, away from the boiler.

Does your boiler show 372?

Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.

* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.

The variants of code 372

The meaning depends on the boiler: find yours below.

372

Repeated loss of flame during calibration

Breakdown: the boiler is stopped Vitodens 100-W B1HF

What our technician checks

  • The ionisation electrode or ignition/monitoring electrode and its connecting cable
  • The plug connections (loose contacts)
  • The flue system and any flue gas recirculation
  • Condensate build-up in the system
  • The inlet of the combined gas valve and its strainer (fouling, visual check)
  • The source of deposits on the electrodes in the boiler room and the flue system (detergents, cleaning or personal care products)
  • After replacing the burner grid and the electrode: cleaning the fan unit, the gas-air duct and the Venturi extension
  • Removing the fan unit before the burner, to avoid water damage