Insufficient gas supply
Breakdown: the boiler is stopped
The boiler is not getting enough gas, for example because a gas valve is closed or the gas pressure is too low. The burner locks out and the boiler only starts again after a reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check that the boiler's gas tap is open.
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show 357?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 357
The meaning depends on the boiler: find yours below.
Insufficient gas supply
What our technician checks
- The main gas valve and the gas shut-off valve (open)
- The static gas pressure and the working gas pressure, measured
- The sizing of the gas line and of the gas flow limiter
- If the static pressure does not drop: the fan unit cable and the coil resistance of the fuel valve (about 4 kΩ)
- The insulation of the ignition electrode
- The tightness of the building's gas pressure regulator, which can raise the pressure when the burner stops and trip the gas flow limiter