Overheating: the temperature monitor has tripped
Blocking: it retries by itself
The temperature monitor has cut the burner because the water in the boiler got too hot, for example because the heat is not carried away to the system well enough. The burner stays blocked while the boiler cools down, then restarts by itself.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Check the system pressure on the display: below 1.0 bar, top up with water or call us.
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show 345?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code 345
The meaning depends on the boiler: find yours below.
The monitoring aquastat has tripped
What our technician checks
- Heat being taken off by the system
- The fill level of the heating system
- The pre-charge pressure of the expansion vessel, matched to the system pressure
- The water flow rate (pump)
- The 3-way diverter valve and venting the system
- If the code appears while heating hot water: fouling and scale in the cylinder or the plate heat exchanger