High-pressure switch open
Breakdown: the boiler is stopped
On an aroTHERM (VWL ../2 A, ../3 A) heat pump, the refrigerant circuit pressure rose above the maximum (41.5 bar): the high-pressure switch stopped the heat pump, which tried three times to restart without success; possible causes are a wrong refrigerant charge, non-condensable particles in the circuit, too high a water flow rate, poor heat transfer or the switch itself. This is a refrigerant circuit fault: the heat pump no longer works normally, and only a trained and certified technician may work on this circuit.
What you can do
- Write down the code shown and the heat pump model (on the rating plate).
- Does the code stay on or come back? Do not take anything apart: call us.
Does your boiler show F.537?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code F.537
The meaning depends on the boiler: find yours below.
HP switch open
What our technician checks
- The refrigerant charge (too much or too little)
- The circuit evacuation (10 mbar) and non-condensable particles
- The high-pressure switch and its electrical connection
- Early expansion of the liquid refrigerant (pressure drop in the refrigerant circuit)
- The water flow rate (above the set maximum) and the flow monitor
- Heat transfer in the heat exchanger