Return warmer than the flow
Breakdown: the boiler is stopped
The boiler measures return water that is warmer than the flow water, which should not happen: sensors swapped, badly placed or faulty, a bad connection, or water flowing the wrong way. On the Calenta Ace, Tzerra Ace, Quinta Ace, Quinta 45-115, Gas 210 Ace, Gas 220 Ace, Gas 320/620 Ace, Calenta Ace-Matic, Tzerra Ace-Matic and Avanta Ace it is a lockout: the boiler stops and only starts again once the cause has been removed and the boiler has been reset.
What you can do
- Write down the code shown and the boiler model (on the rating plate).
- Reset the boiler once only.
- If the code comes back, do not keep trying and do not take anything apart: call us.
Does your boiler show E01.12?
Repair visit: 180 € excl. VAT (190.80 € incl. 6 % VAT*), first hour included, parts excluded.
* 6 % VAT: work on a private home more than 10 years old, invoiced to a private person. Without a written objection within a month of the invoice, you confirm that these conditions are met; otherwise the VAT is 21 % and the responsibility is yours.
The variants of code E01.12
The meaning depends on the boiler: find yours below.
The temperature measured by the return sensor is higher than the flow temperature.
Return > Flow
The temperature measured by the return sensor is higher than the flow temperature.
Return > Flow
The return temperature value is higher than the flow temperature
What our technician checks
- The sensors' wiring and connectors
- Which way round the sensors are fitted and where the flow sensor sits
- The direction the water flows: pump and valves
- The return temperature in the boiler
- The sensors' operation and resistance value
- The sensor, replaced if faulty
- If the fault persists: resetting CN1/CN2, then the circuit board